DG180 — Centrifugal Fan

SUNXFAN DG180 series: 4 models. All figures below are manufacturer datasheet values.

Model matrix

Model Airflow Max static pressure Voltage Power Speed Noise Speed control
DG180A-E092E1-01 960 m³/h 360 Pa 115 V AC 175 W 1320 r/min 66 dB(A) 0-10V/PWM / 4-speed
DG180A-E092E3-01 960 m³/h 360 Pa 230 V AC 175 W 1320 r/min 66 dB(A) 0-10V/PWM / 4-speed
DG180B-E092D1-01 780 m³/h 330 Pa 115 V AC 120 W 1350 r/min 67 dB(A) 0-10V/PWM / 3-speed
DG180B-E092D3-01 780 m³/h 330 Pa 230 V AC 120 W 1350 r/min 67 dB(A) 0-10V/PWM / 3-speed

DG180A-E092E1-01 — EC180 Single inlet Centrifugal Fan — 960 m³/h

Specifications

FAQ

Q: When is a 330–360 Pa, high-airflow blower the right choice?

A: When the resistance is short and honest: condensing-unit discharge, appliance exhaust up a short stack, cabinet air exchange through a grille and maybe one bend. 780–960 m³/h at 330–360 Pa moves serious volume through such paths without paying the noise and power premium of a high-pressure wheel fighting an open system. The mistake to avoid is the reverse: a 700 Pa-class blower on a 150 Pa system rides far off its design point, wastes energy and sounds harsh.

Q: 4-speed taps or 0-10V/PWM — how do I choose?

A: The 4-speed taps serve uncontrolled installs: a technician sets one point with a jumper or switch — kitchen boost, condenser duty, appliance exhaust — and the fixed steps guarantee repeatable airflow and noise. 0-10V/PWM is for when a controller or BMS will trim speed against a sensor. On fixed duty, land the tap on your actual system curve rather than defaulting to the fastest: each step down buys several dB(A) and a cubic saving in power.

Q: What does the PP impeller contribute here?

A: Glass-fibre-filled polypropylene keeps wheel mass low: gentle bearing loads over years of continuous running and little start inertia for the EC motor. It is intrinsically corrosion-proof — salt air, humidity and cleaning-agent traces that pit coated steel leave it untouched, which is why appliance and marine-air-conditioning duty favours it. The honest trade is temperature: respect the −25 ~ +60 °C envelope; for airstreams that live near that ceiling, specify a steel-wheel blower instead.

DG180A-E092E3-01 — EC180 Single inlet Centrifugal Fan — 960 m³/h

Specifications

DG180B-E092D1-01 — EC180 Single inlet Centrifugal Fan — 780 m³/h

Specifications

DG180B-E092D3-01 — EC180 Single inlet Centrifugal Fan — 780 m³/h

Specifications